Basic Info
  • Model NO.: YKSY
  • Conductor Type: Stranded
  • Conductor Material: Copper
  • Insulation Material: PVC
  • Range of Application: Distribution
  • Brand: Boan
  • Rated Voltage: 0.6/1 Kv
  • Size: 1.5-10 mm2
  • Trademark: DingAn or OEM
  • Specification: IEC/HD
  • HS Code: 8544492100
  • Type: Insulated
  • Application: Underground
  • Sheath Material: PVC
  • Material Shape: Round Wire
  • Certification: ISO9001, CE, CCC
  • Manufacture Standard: IEC 60502-1/HD 603
  • Class of Conductor: 1
  • Number of Cores: 7-37
  • Transport Package: Fumigated Steel-Wooden Drum/Steel Drum
  • Origin: Jiangsu Yixing, China
Product Description
YKSY, Power Cable, 0.6/1 KV, Cu/PVC/PVC (IEC 60502-1/HD 603)
Underground cable with PVC insulation and PVC sheath, multi-core
Structure
1 Copper conductor, round solid (RE)
2 Core insulation (PVC)
3 Inner covering (EPDM)
4 Sheath (PVC black, UV-resistant)

Application
Power and control cables in power stations, industrial installations and switchgears. For fi xed installation underground, in interior premises, cable ducts, in the open air, in water - as permitted by the local building regulations - if no risk of any mechanical damage is to be expected.

Technical Data
Rated voltage: 0.6/1 kV
Test voltage: 3.5 kV/50 Hz

Temperature range:
laying temperature: min. -5 °C
operating temperature: -30 °C up to +70 °C
conductor temperature: max. +70 °C
short-circuit temperature: max. +160 °C/5 s
 
Bending radius (min.):
12 x φ of cable
 
Core identifi cation:
HD 308 S2
 
Fire properties:
fl ame retardant:
EN 60332-1-2
 
Number of cores x nominal cross sectionMax. conductor resistanceCurrent rating in the groundCurrent rating in the airOuter diameterTotal weight
(mm²)(Ω/km)(A)(A)(mm)(kg/km) 
E-XAYY
7 x 1.5 RE12.100161213.9330
10 x 1.5 RE12.100131017.1430
14 x 1.5 RE12.10012918.4550
19 x 1.5 RE12.111920.2695
24 x 1.5 RE12.19823.4845
30 x 1.5 RE12.18724.71,010
37 x 1.5 RE12.1008727.11,170
48 x 1.5 RE12.17631.21,460
61 x 1.5 RE12.17634.01,970
7 x 2.5 RE7.41211715.1450
10 x 2.5 RE7.41181418.7565
14 x 2.5 RE7.41161320.1735
19 x 2.5 RE7.41141122.2930
24 x 2.5 RE7.41121025.81,140
30 x 2.5 RE7.4111927.41,420
37 x 2.5 RE7.4111930.11,710
7 x 4 RE4.61272217.7605
10 x 4 RE4.61231822.5795
7 x 6 RE3.08352819.2770
7 x 10 RE1.83473821.91,160

 