Jiangsu, China
Business Type:
Year of Establishment:
Plant Area:
124154 square meters
Management System Certification:
ISO9001:2008, ISO14001:2004, OHSAS18001:2007
Annual Revenue:
421.24 Million USD
OEM/ODM Service
Sample Available

XLPE Cable, Copper Cable, Power Cable manufacturer / supplier in China, offering N2xsy, Power Cable, 6/10 Kv, 1/C, Cu/XLPE/Cws/Cts/PVC (HD 620 10C/VDE 0276-620), Yy PVC Control Cable, 300/500 V, Flexible Cu/PVC/PVC (BS 6500), ACSR/Aw, Aluminium Conductors Aluminium Clad Steel Reinforced (IEC 61089) and so on.

Gold Member Since 2013
Audited Supplier
Supplier Homepage Products MV Power Cable European Standard MV Power Cable N2xsy, Power Cable, 6/10 Kv, 1/C, Cu/XLPE/Cws/Cts/PVC (HD 620 10C/VDE 0276-620)

N2xsy, Power Cable, 6/10 Kv, 1/C, Cu/XLPE/Cws/Cts/PVC (HD 620 10C/VDE 0276-620)

Get Latest Price
Min. Order / Reference FOB Price
100 Meters US $5-60/ Meter
Production Capacity: 12000 Km/Year
Transport Package: Fumigated Steel-Wooden Drum/Steel Drum
Payment Terms: L/C, T/T, D/P, Paypal, Western Union
Application: Construction, Industrial, Power Station
Voltage: Low and Medium Voltage Cable
Current: DC Cable
Insulation Material: XLPE
Sheath Material: PVC
Material Shape: Round Wire

You Might Also Like


Basic Info

Model NO.: N2XSY
Wire Core Material: Bare Copper Wire
Certification: ISO, CCC
Model: N2xsy
Brand: Boan
Manufacture Standard: HD 620 10c/VDE 0276-620
Rated Voltage: 6/10 Kv
Size: 35-500 mm2
Number of Cores: 1
Type of Screen: Copper Wire
Trademark: DingAn
Specification: SGS
Origin: Jiangsu Yixing, China
HS Code: 8544601200

Product Description

N2XSY, Power Cable, 6/10 KV, 1/C, CU/XLPE/CWS/CTS/PVC (HD 620 10C/VDE 0276-620)

Technical Data:
conductor material: bare copper
conductor construction: stranded, class 2
insulation: XLPE DIX8
sheathing material: PVC DMV6
flame retardant: VDE 0482-332-1-2/IEC 60332-1
maximum temperature at conductor: 90 °C
max. operating temperature, fixed: +70 °C
temperature, moved/during installation: -5 - +70 °C
bending radius, fixed installation: 15 x DA
partial discharge: 2 pC
nominal voltage Uo: 6 kV
nominal voltage U: 10 kV

maximum permitted operating voltage in 3-phase systems:12 kV
test voltage: 21 kV

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and
distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc.

Number of cores and cross-section
Shape of conductorConductor diameterNominal insulation thicknessDiameter over insulationNominal thickness sheathOuter diameter (approx.)Bending radius (min.)Weight (approx.)